Power Line Carrier ____________________________________________________________________
RF-MCGARDPRO
Hubbell Power Systems, Inc.
–
RFL™
Products
July 1, 2022
©2022 Hubbell Incorporated
5-25
6.
TX Logic Bus Start Bit:
The range of TX logic bus start bits can be set from 3 to 511
in increments of 1.
7.
TX Logic Bus Length:
The TX logic bus length can be set from 0 to 24 in increments
of 1.
8.
RX Logic Bus Start Bit:
The range of RX logic bus start bits can be set from 3 to 511
in increments of 1.
9.
RX Logic Bus Length:
The RX logic bus length can be set from 0 to 24 in increments
of 1.
Recommended On/Off Settings
RFL recommends the following settings for most standard PLC On/Off applications. Be aware
that the “Logic Options” and “Logic Timer” settings may vary by logic.
Table 5-9 Recommended On/Off Settings
User Interface Web Page (Path)
Setting Name
Direct Comparison
Blocking (DCB)
Configuration > PLC> (General)
Module Enable
ON
Transmitter
Configuration > PLC> (General)
TX Block Frequency
-
Configuration > PLC> (General)
TX Reserve Level
1 W
Configuration > PLC> (General)
TX Block Level
10 W
Configuration > PLC> (General)
Local Tx Causes Block
Yes
Configuration > PLC> (General)
Reflected Power Alarm Threshold
20%
Receiver
Configuration > PLC> (General)
RX Block Frequency
-
Configuration > PLC> (General)
RX Bandwidth
1000 Hz
Configuration > PLC> (General)
Block Hold Timer
3 ms
Start/Stop Polarity
Configuration > PLC> (General)
Start 1 Polarity
Normal
Configuration > PLC> (General)
Start 2 Polarity
Normal
Configuration > PLC> (General)
Start Logic
Or
Configuration > PLC> (General)
Stop 1 Polarity
Normal
Configuration > PLC> (General)
Stop 2 Polarity
Normal
Configuration > PLC> (General)
Stop Logic
Or
Advanced
Configuration > PLC> (Advanced)
Function
On/Off
Configuration > PLC> (Advanced)
Discriminator Energy Threshold
15