Output Test
Menu location: Test > Outputs. Select the output to be tested.
The following web page is used to verify the correct function of the relay outputs.
1
2
3
4
5
6
Represents the Output
number of the I/O module
Description of outputs as entered on the
Label Enable Configuration webpage
Figure 4-30. Output Test
1.
TB#/State:
Indicates the terminal block number of the output function and whether the
output is activated. This can be thought of as ‘after’ the logic bit associated with the
output. The field is updated dynamically.
2.
Logic State:
Indicates the state of the logic bit associated with the output. This can be
thought of as ‘before’ the terminal block state. This field is updated dynamically.
3.
Action:
This drop-down menu allows the tester to set the outputs to the following modes:
•
Normal:
This is the normal operating condition for the output. The logic bus drives
the output.
•
Hold:
This will lock the output to the state of the output when the test is executed.
•
Off:
Sets the output to a low state (0), independent of the status of the logic bit.
➢
An output that is set for a normally closed contact will close.
➢
An output that is set as a normally open contact will open.
See
•
On:
Sets the output to a high state (1), independent of the status of the logic bit.
➢
An output that is set for a normally closed contact will open.
➢
An output that is set as a normally open contact will close.
See