Power Line Carrier ____________________________________________________________________
RF-MCGARDPRO
Hubbell Power Systems, Inc.
–
RFL™
Products
July 1, 2022
©2022 Hubbell Incorporated
5-29
Configuration > PLC> (Checkback)
Test 4 TX Level
Low
Low
Configuration > PLC> (Checkback)
Test 5 Command
Off
Off
Configuration > PLC> (Checkback)
Test 5 Response
Off
Off
Configuration > PLC> (Checkback)
Test 5 TX Level
Low
Low
Configuration > PLC> (Checkback)
Test 6 Command
Off
Off
Configuration > PLC> (Checkback)
Test 6 Response
Off
Off
Configuration > PLC> (Checkback)
Test 6 TX Level
Low
Low
Configuration > PLC> (Checkback)
Test 7 Command
Off
Off
User Interface Web Page (Path)
Setting Name
Station A
Station B
Configuration > PLC> (Checkback)
Test 7 Response
Off
Off
Configuration > PLC> (Checkback)
Test 7 TX Level
Low
Low
Configuration > PLC> (Checkback)
Test 8 Command
Off
Off
Configuration > PLC> (Checkback)
Test 8 Response
Off
Off
Configuration > PLC> (Checkback)
Test 8 TX Level
Low
Low
Configuration > PLC> (Checkback)
Remote Checkback Initiate
16
16
5.4.2.5.2 Recommended Checkback Settings (Three Terminal)
RFL recommends the following settings for most standard PLC Checkback Three-Terminal line
testing operations.
Master
Remote
Station A
Station C
Remote
Station B
Table 5-11 Recommended Checkback Settings, 3-Terminal Line Testing
User Interface Web Page (Path)
Setting Name
Station A
Station B
Station C
Configuration > PLC> (Checkback)
Enable/Mode
Master
Remote
Remote
Configuration > PLC> (Checkback)
Max Delay for Remote Response
30 s
30 s
30 s
Configuration > PLC> (Checkback)
Start Time
6:00
6:00
6:00
Configuration > PLC> (Checkback)
Interval
24 h
24 h
24 h
Configuration > PLC> (Checkback)
Test 1 Command
1
1
Off
Configuration > PLC> (Checkback)
Test 1 Response
1
1
Off
Configuration > PLC> (Checkback)
Test 1 TX Level
High
High
Low
Configuration > PLC> (Checkback)
Test 2 Command
2
2
Off
Configuration > PLC> (Checkback)
Test 2 Response
2
2
Off
Configuration > PLC> (Checkback)
Test 2 TX Level
Low
Low
Low
Configuration > PLC> (Checkback)
Test 3 Command
3
Off
3
Configuration > PLC> (Checkback)
Test 3 Response
3
Off
3