– Binary Output
Configuration > DNP > Type 10 – Binary Output
This page lists any DNP Type 10 Binary Outputs points available for reporting. System Logic
HMI Inputs are always available. Points from different sources are organized on separate tabs.
Figure 4-56. DNP Configuration – Type 10 – Binary Output
Type 20
– Counter
Configuration > DNP > Type 20 – Counter
NOTE:
Only those SOE Triggers which are enabled for recording in the Config > SOE page are
displayed in this page.
This page lists any DNP Type 20 Counter points available for reporting. System Logic SOE
Trigger Counters are always available. Additional points may be available when DNP-enabled
modules are installed. Points from different sources are organized on separate tabs.
If the SOE triggers are configured for DNP in this page, and the user enables more SOE triggers
in the Config > SOE page at a later time, those newly enabled SOE triggers will be disabled by
default. Therefore, index numbers won’t change if using Auto-index mode.
If an SOE trigger is enabled for DNP recording/reporting, the control to enable/disable the SOE
trigger in the Config > SOE page will be disabled. Any SOE trigger which is enabled for DNP