Item
900 kVA
1000 kVA
1100 kVA
1200 kVA
Bypass input Bypass input
current (A)
1367
1519
1671
1823
Recomme
nded
cross-
sectional
area
(mm
2
)
L1
5 x 240
5 x 240
6 x 240
6 x 240
L2
5 x 240
5 x 240
6 x 240
6 x 240
L3
5 x 240
5 x 240
6 x 240
6 x 240
N
5 x 240
5 x 240
6 x 240
6 x 240
PE
2 x 240
2 x 240
2 x 240
2 x 240
Output
Output current (A) 1367
1519
1671
1823
Recomme
nded
cross-
sectional
area
(mm
2
)
U
5 x 240
5 x 240
6 x 240
6 x 240
V
5 x 240
5 x 240
6 x 240
6 x 240
W
5 x 240
5 x 240
6 x 240
6 x 240
N
5 x 240
5 x 240
6 x 240
6 x 240
PE
2 x 240
2 x 240
2 x 240
2 x 240
Battery
input (lead-
acid battery)
Nominal battery
discharge current
(A)
1995
2216
2438
2660
Maximum battery
discharge current
(A)
2389
2654
2920
3185
Recomme
nded
cross-
sectional
area
(mm
2
)
+
6 x 240
6 x 240
6 x 240
6 x 240
-
6 x 240
6 x 240
6 x 240
6 x 240
PE
2 x 240
2 x 240
2 x 240
2 x 240
Battery
input
(SmartLi)
Nominal battery
discharge current
(A)
1870
2078
2286
2493
Maximum battery
discharge current
(A)
2347
2607
2868
3129
Recommended
cross-sectional
area
For details, see the IEC-60364-5-52 specifications and
SmartLi User Manual
.
Equipotentia
l ground
point
Recommended
cross-sectional
area (mm
2
)
16
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
6 Installation
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
99