Optional
Component
Model
Function
Bottom cabling
cabinet
-
Applies to the bottom cabling scenario.
Transfer copper bar
for bottom cabling
-
Top cabling
component
-
Applies to the top cabling scenario.
Inductor cabinet
-
An inductor cabinet is required when
the UPS is the three-phase three-wire
model.
NO TE
The ECM extended subrack does not support onsite installation. If you require this optional
component, inform Huawei when you purchase the UPS so that Huawei can install the
subrack before delivery.
5.2 Dry Contact Extended Card
The dry contact extended card provides five groups of electric relay output ports
for dry contact signals and five groups of signal input ports to implement various
alarm and control functions as required.
A maximum of one dry contact extended card supported in the power monitoring
subrack. The card is hot swappable.
Figure 5-1 Appearance
NO TICE
For dry contact outputs, the rated DC voltage and current are 24 V DC and 0.6 A
and the maximum values are 30 V DC and 1.0 A. The rated AC voltage and current
are 24 V AC and 0.6 A and the maximum values are 30 V AC and 1.0 A. During
cable connection, ensure that the voltage and current do not exceed these
maximum values.
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
5 Optional Components
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
68