Figure 7-7 S-ECO mode parameters 2
Figure 7-8 S-ECO mode parameters 3
Step 3 (Optional) If you set S-ECO mode in bypass mode, manually start the UPS
inverter.
NO TICE
After the inverter is started, the UPS still supplies power through the bypass, and
the inverter is standby. When the bypass is abnormal, the UPS transfers to inverter
mode immediately. If the inverter is not started, the UPS stops supplying power
when the bypass is abnormal, and the system may power off.
Figure 7-9 S-ECO system status (VFI)
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
7 Single UPS Commissioning
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
338