Figure 4-17 Appearance
(1) Status indicator
(2) LCD touchscreen
Table 4-16 Indicator status
Status
Color
Meaning
On
Red
A critical alarm has been generated, and the buzzer
sounds continuously.
Yellow
A minor alarm has been generated, and the buzzer
buzzes intermittently at 2 Hz.
Green
The UPS is running properly or a warning has been
generated.
Off
-
The MDU is powered off.
NO TE
The indicator on the MDU panel is yellow when the bypass supplies power in non-ECO
mode.
Figure 4-18 MDU ports