Procedure
Step 1 On the WebUI, choose Monitoring > UPS System > Running Parameter >
System Settings, and set Paral sys hibernate to Enable.
Step 2 Set Module cycle hiber period(d) to an integer ranging from 1 to 100. The
default value is 30.
Figure 7-27 System settings
NO TE
Click Submit after setting parameters on the WebUI.
----End