Figure 4-2 Appearance
(1) Running indicator
(2) Battery cold start button
(3) Alarm indicator
(4) Ready switch
(5) Fault indicator
(6) Bypass modules
(7) Bypass control module
(8) Auxiliary power supply
(9) Crowbar
Table 4-3 Indicator description
Indicator
Color
Status
Description
Running
indicator
Green
Steady on
The system is working in bypass mode.
Blinking
slowly
The bypass has no output (blinking at
0.2 Hz, on for 2.5s and off for 2.5s).
Blinking
fast
The bypass is not configured or the
software is being upgraded (blinking at
4 Hz, on for 0.125s and off for 0.125s).
Off
The bypass software is being upgraded.
Alarm
indicator
Yellow
Steady on
A minor alarm is generated for the
bypass.
Off
There is no minor alarm for the bypass,
or the software is being upgraded.
Fault
indicator
Red
Steady on
A critical alarm is generated for the
bypass.
Off
There is no critical alarm for the bypass,
or the software is being upgraded.
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
4 Component Description
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
51