(4) Expansion sleeve
(5) Expansion nut
(6) Concrete floor
Step 3 Combine the UPS with the bottom cabling cabinet.
1. Remove the screws preinstalled on the copper bars in power cabinet 2 and
store them for future use.
Figure 6-339 Removing the preinstalled screws
2. Move the UPS cabinets to the installation positions.
3. Remove the power distribution covers from power cabinets 1 and 2.
Figure 6-340 Removing covers
4. Combine power cabinet 1 with other cabinets in the sequence of bottom, top,
and middle. (Remove the rear door of power cabinet 1 when installing the
cabinet combination screws in the middle at the rear of the cabinet.).
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
6 Installation
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
278