NO TICE
Set system parameters with caution because the settings determine whether the
UPS can operate normally.
● Set Single/Parallel after double check. Incorrect settings may affect the normal
UPS operation.
● Output voltage level refers to the line voltage level. Set it based on site
requirements.
● Set Output frequency correctly. Otherwise, loads may be affected and the UPS
may not work properly.
● Set all battery parameters correctly based on site requirements. Battery
parameter settings are critical to battery maintenance, battery lifespan, and
UPS discharge time.
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
7 Single UPS Commissioning
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
328