Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System
Handling Suggestion
0061-01 Inverter
alarm
Minor
Manual
/Power-
off/
Automa
tic
The UPS shuts down.
The UPS may transfer to
another working mode or
shut down.
Possible causes:
● Parallel cables are
incorrectly
connected.
● The lengths of
parallel cables vary
greatly.
Measures:
● Reconnect cables.
● The lengths of
parallel cables vary
within a range of
5%.
0061-02 Inverter
alarm
Minor
Manual
/Power-
off
N/A
Possible cause: The
EEPROM chip is faulty.
Measure: Contact
Huawei technical
support for repair.
0061-09 Inverter
alarm
Minor
Automa
tic
The UPS may transfer to
another working mode or
shut down.
Possible causes:
● There is a strong
interference source
onsite.
● An internal fault
occurs in the UPS.
Measures:
● Check and isolate the
strong interference
source onsite.
● Contact Huawei
technical support.
0064-01 OL
timeout
Critical
Automa
tic
The UPS automatically starts
after shutdown.
The UPS may transfer to
another working mode or
shut down.
Possible cause: The load
exceeds the rated
inverter loading
capacity.
Measure: Reduce the
load or replace the UPS
with a larger-capacity
UPS.
UPS2000-G- (6 kVA-20 kVA)
User Manual
D Alarm Handling
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
164