Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System
Handling Suggestion
0136-01 Faulty
tempera
ture
and
humidit
y
module
Minor
Possible causes: The
temperature and
humidity module is
faulty.
Measures:
● Check parameter
settings of the
temperature and
humidity transducer.
● Replace the
temperature and
humidity transducer.
0158-01 On
bypass
Minor
Automa
tic
If the bypass is abnormal,
the UPS may power off.
Possible causes:
● The inverter is not
started.
● The load exceeds the
rated inverter
loading capacity.
● The inverter is faulty.
Measures:
● Check whether other
alarms are
generated. If yes, see
the other handling
methods.
● If no, start the UPS
manually.
UPS2000-G- (6 kVA-20 kVA)
User Manual
D Alarm Handling
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
171