Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System
Handling Suggestion
0049-01 Battery
qty.
wrong
Minor
Manual
/Power-
off/
Automa
tic
An alarm is displayed, and
the battery service life may
be shortened.
Possible causes:
● The number of
batteries is
incorrectly set.
● Batteries are
damaged.
● If batteries are fully
charged, reconnect
the batteries as soon
as the system powers
off.
Measures:
● Check whether the
number of batteries
is correctly set.
● Check whether
batteries are
damaged.
● After ensuring that
the number of
batteries is correct,
clear the alarm.
0060-01 Inverter
fault
Critical
Power-
off
The inverter shuts down. The
UPS transfers to bypass
mode or has no output
based on the transfer logic.
Possible cause: The
inverter is faulty.
Measure: Contact
Huawei technical
support for repair.
0060-02 Inverter
fault
Critical
Power-
off
The UPS shuts down.
The UPS may transfer to
another working mode or
shut down.
Possible cause: The
inverter relay is faulty.
Measure: Contact
Huawei technical
support for repair.
0060-03 Inverter
fault
Critical
Power-
off
The UPS shuts down.
The UPS may transfer to
another working mode or
shut down.
UPS2000-G- (6 kVA-20 kVA)
User Manual
D Alarm Handling
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.