![background image](http://html.mh-extra.com/html/huawei/ups2000-g-series/ups2000-g-series_user-manual_166640142.webp)
Mai
n
Men
u
Second-
Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Value Range
Preset Value
Faulty UPS
(Dry
contact)
-
Dry contacts 1–6
Dry contact 6
System
Paramete
rs
Parallel
(configurabl
e after the
inverter
shuts down)
Single/
Parallel
Single and Parallel
Single
Redundant
UPSs
0–3
0
Output
(configurabl
e after the
inverter
shuts down)
Output mode
(configurable
only on the
UPS2000-
G-15 kVA/20
kVA)
Single-phase/Three-
phase
Three-phase (on the
UPS2000-G-15 kVA/20
kVA)
Voltage level
● 208 V, 220 V, 230 V,
and 240 V (on the
UPS2000-G-6
kVA/10 kVA)
● 208 V, 220 V, 230 V,
and 240 V, single-
phase (on the
UPS2000-G-15
kVA/20 kVA)
● 380 V, 400 V, and
415 V, three-phase
(on the UPS2000-
G-15 kVA/20 kVA)
● 220 V (on the
UPS2000-G-6
kVA/10 kVA)
● 220 V, single-phase
(on the UPS2000-
G-15 kVA/20 kVA)
● 380 V, three-phase
(on the UPS2000-
G-15 kVA/20 kVA)
Frequency
level
50 Hz, 60 Hz, and
Automatic
50 Hz
Converter
mode
Enabled and Disabled
Disabled
Output
(configurabl
e in any
mode)
Volt. adj. coef. ±5%, ±4%, ±3%, ±2%,
±1%,0%
0%
Bypass
(configurabl
e after the
inverter
shuts down)
Max. voltage
10%, 15%, 20%, 25%,
and 30%
15%
Min. voltage
10%, 20%, 30%, 40%,
50%, and 60%
20%
UPS2000-G- (6 kVA-20 kVA)
User Manual
C LCD Menus and Parameters
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
134