Model
Wiring
Terminal
Number
of
Phases
Rated
Voltage
Externa
l Circuit
Breaker
Cable
Cross-
Sectional
Area
Terminal
Type
Torque
for
Tighteni
ng Bolts
Battery
-
± 240 V DC
63 A
16 mm
2
16 mm
2
M6 90°
OT
terminal
4.8 N·m
Output
1
220 V
AC/230 V
AC/240 V
AC
125 A
(feature
D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8 N·m
20 kVA
(three-
phase
input
three-
phase
output)
Bypass
input
3
380 V
AC/400 V
AC/415 V
AC
63 A
(feature
D)
10 mm
2
10 mm
2
M6 OT
terminal
2.8 N m
Mains input 3
Battery
-
± 240 V DC
63 A
16 mm
2
16 mm
2
M6 90°
OT
terminal
4.8 N·m
Output
3
380 V
AC/400 V
AC/415 V
AC
63 A
(feature
D)
10 mm
2
10 mm
2
M6 OT
terminal
2.8 N m
NO TE
● If customers purchase input and output power cables by themselves, use the cables that
comply with standards proposed by Underwriters Laboratories (UL) or International
Electrotechnical Commission (IEC).
● Two-mains-input scenarios are not supported on the UPS2000-G-15 kVA/20 kVA (single-
phase input single-phase output).
3.1.4 Unpacking and Checking
shows the transportation safety requirements.
Figure 3-6 Transportation safety requirements
UPS2000-G- (6 kVA-20 kVA)
User Manual
3 Installation
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
34