Item
Description
Default Value
Value Range
Overcurre
nt thres.
Set an alarm threshold for
battery overcurrent. The
parameter is configurable in
any mode.
Note: The overcurrent alarm
threshold can be set only
for the UPS2000-G-15
kVA/20 kVA.
Standard
model: 3.0 A
Long backup
time model:
6.0 A
Standard
model: 2.0–4.0
A
Long backup
time model:
4.0–8.0 A
●
Equalized Charge screen
Figure 4-37 Equalized Charge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Table 4-27 Equalized Charge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Item
Description
Default
Value
Value Range
Equalized
charging
Determine whether to enable
equalized charging. The
parameter is configurable in
any mode.
Enabled
Disabled,
Enabled
Time
interval
Set the time interval for
equalized charging. The
parameter is configurable in
any mode.
60 days
30–180 days
Voltage
Set the battery equalized
voltage. The parameter is
configurable in any mode.
2.35 V/cell
2.33–2.40 V/cell
Max. time Set the maximum equalized
charge time. The parameter
is configurable in any mode.
960 min
600–999 min
Figure 4-38 Equalized Charge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
UPS2000-G- (6 kVA-20 kVA)
User Manual
4 Control Panel
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
73