Mai
n
Men
u
Second-
Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Value Range
Preset Value
Battery
capacity
(configurable
in non-
battery
mode)
7–1000 Ah
● For the UPS2000-
G-6 kVA, the
default value is 7
Ah on a standard
model and 40 Ah
on a long backup
time model.
● For the UPS2000-
G-10 kVA, the
default value is 9
Ah on a standard
model and 65 Ah
on a long backup
time model.
● For the UPS2000-
G-15 kVA/20 kVA,
the default value is
65 Ah on a long
backup time model.
Intelli.
Hibernation
Enabled and Disabled
Disabled
Overtemp.
thres.
45–55°C
50°C
Undertemp.
thres.
–30°C to +5°C
–5°C
Charge curr.
limit
(UPS2000-
G-15KRTL-01/
UPS2000-
G-20KRTL-01)
● 1.0–2.0 A (standard
model)
● 1.0–4.0 A (long
backup time
model)
2.0 A
Overcurrent
thres.
(configurable
only for the
UPS2000-
G-15 kVA/20
kVA)
● 2.0–4.0 A (standard
model)
● 4.0–8.0 A (long
backup time
model)
● 3.0 A (standard
model)
● 6.0 A (long backup
time model)
Battery string
sharing
Enabled and Disabled
Disabled
Equalized
Charge
Equalized
charging
Enabled and Disabled
Enabled
UPS2000-G- (6 kVA-20 kVA)
User Manual
C LCD Menus and Parameters
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
137