Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System
Handling Suggestion
0060-04 Inverter
fault
Critical
Power-
off
The UPS shuts down
immediately, supplies no
power, and protects loads.
Possible cause: The
inverter output is short-
circuited.
Measure: Rectify output
port short circuits. After
you clear the alarm,
restart the UPS. If the
alarm persists, contact
Huawei technical
support for repair.
0060-05 Inverter
fault
Critical
Automa
tic
The UPS shuts down.
The UPS may transfer to
another working mode or
shut down.
Possible causes:
● The mains
experiences
instantaneous high-
voltage impact.
● The output has
special loads such as
sensitive loads and
rectification loads.
● The output has
transformer loads
but the transformer
mode is not set.
● The hardware is
faulty.
Measures:
● After you rectify the
fault, restart the UPS.
● Check whether the
load type is
supported by the
UPS.
● Enable the
transformer mode.
● Contact Huawei
technical support for
repair.