NO TE
The upper and lower thresholds are configurable on the LCD.
9.5 Output Electrical Specifications
Table 9-7 Output Electrical Specifications
Item
6 kVA
10 kVA
15 kVA
20 kVA
Rated capacity
6 kVA
10 kVA
15 kVA
20 kVA
Output power
factor (PF)
0.9
Rated output
voltage
208 V AC, 220 V AC, 230 V
AC, or 240 V AC (single-
phase output; select a
voltage system by setting a
voltage level on the LCD.)
● 208 V AC, 220 V AC, 230
V AC, or 240 V AC (single-
phase output; select a
voltage system by setting
a voltage level on the
LCD.)
● 380 V AC, 400 V AC, or
415 V AC (three-phase
output; select a voltage
system by setting a
voltage level on the LCD.)
Output voltage
tolerance
±1%
Total harmonic
distortion of
output voltage
(THDv)
< 4% (non-linear load)
< 2% (resistive load)
Crest factor
A maximum of 3:1
Inverter overload
capability
● 105% ≤ load < 125%: transfer to bypass mode after 5
minutes
● 125% ≤ load < 150%: transfer to bypass mode after 1
minute
● Load ≥ 150%: transfer to bypass mode after 100
milliseconds
The UPS stops supplying power if the bypass is
abnormal.
Dynamic voltage
tolerance
±5%
Output voltage
unbalance
-
● ±1% (balanced load)
● ±3% (unbalanced load)
UPS2000-G- (6 kVA-20 kVA)
User Manual
9 Technical Specifications
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
117