Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System
Handling Suggestion
0008-01 Rect.
start
overlimi
t
Minor
Manual
/Power-
off
The UPS cannot start.
Possible cause: The
mains voltage
frequently becomes
abnormal during
startup.
Measure: Check the
mains input voltage. If
the voltage becomes
normal, clear the alarm
and restart the UPS.
0010-01 Abnorm
al BPS
volt.
Minor
Automa
tic
The UPS cannot transfer to
bypass mode. If the bypass is
supplying power, the UPS
changes the working mode.
Possible causes:
● The bypass input
voltage is abnormal.
● The bypass input
frequency is
abnormal.
Measures:
● Check whether the
bypass input voltage
exceeds the
configured range. If
yes, change the
range or wait until
the bypass input
recovers.
● Check whether the
bypass input
frequency exceeds
the configured range.
If yes, change the
range or wait until
the bypass input
recovers.
0010-02 Abnorm
al BPS
volt.
Minor
0011-01 BPS
phase
reverse
Minor
Automa
tic
● If the inverter has not
started, the system has
no output, and inverter
startup is prohibited.
● If the inverter has started,
the inverter still works
properly, but the system
cannot transfer to bypass
mode.
Possible cause: The
bypass input three-
phase sequence is
incorrect.
Measure: Check that
bypass input power
cables are correctly
connected.
UPS2000-G- (6 kVA-20 kVA)
User Manual
D Alarm Handling
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
145