Item
Expected Result
Measures
Maintenance Interval
Battery
operating
temperature
1. The ambient
battery
temperature is
25±5°C.
2. The battery
operating
temperature is
lower than battery
temperature
+ 20°C.
3. Battery charge and
discharge
conditions meet
the requirements
specified in the
battery
specifications.
1. Identify the cause of
the abnormal battery
operating
temperature.
2. If the fault persists,
contact Huawei
technical support.
Monthly
Charge voltage
of battery
string
● Equalized voltage
14.1 V x Number of
batteries (tolerance
±1%)
● Float voltage 13.5
V x Number of
batteries (tolerance
±1%)
1. If the voltage drop
between the battery
string output
terminals and the
battery input terminals
at the UPS side is
greater than 1% of the
battery string voltage,
check whether the
cable between the
battery string and the
UPS is excessively
long, or the cable
diameter is excessively
small.
2. Check whether the
equalized charging
voltage and float
charging voltage are
correctly set for the
UPS.
3. If the fault persists,
contact Huawei
technical support.
Monthly
UPS2000-G- (6 kVA-20 kVA)
User Manual
7 Routine Maintenance