Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System
Handling Suggestion
0044-03 Incomp
atible
ver.
Critical
Manual
/Power-
off
The UPS cannot be started.
Possible cause: Software
and hardware versions
do not match.
Measure: Contact the
manufacturer to load
software.
0044-04 Incomp
atible
ver.
Critical
Manual
/Power-
off
The UPS cannot be started.
Possible cause: An error
occurred during
software loading.
Measure: Contact the
manufacturer to load
software.
0044-05 Incomp
atible
ver.
Critical
Manual
/Power-
off
The UPS cannot be started.
Possible cause: Software
and hardware versions
do not match.
Measure: Contact the
manufacturer to load
software.
0044-06 Incomp
atible
ver.
Critical
Manual
/Power-
off
The UPS cannot be started.
Possible cause: Software
and hardware versions
do not match.
Measure: Contact the
manufacturer to load
software.
0045-03 Charger
alarm
Critical
Manual
/Power-
off
The charger in the UPS
stops.
Possible cause: The
charger capacitor is
faulty.
Measure: Contact
Huawei technical
support for repair.
UPS2000-G- (6 kVA-20 kVA)
User Manual
D Alarm Handling
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
159