![background image](http://html.mh-extra.com/html/huawei/ups2000-g-series/ups2000-g-series_user-manual_166640079.webp)
Item
Description
Default Value
Value Range
Battery
capacity
Set the battery string
capacity. Battery capacity is
the sum of all battery
capacities, set the
parameters based on the
actual battery capacity. The
parameter is configurable
in non-battery mode or
non-battery ECO mode.
65 Ah
7–1000 Ah
Intelli.
Hibernati
on
When it is set to enabled,
the intelligent battery
hibernation function is
enabled. The parameter is
configurable in any mode.
Disabled
Disabled,
Enabled
Overtemp
. thres.
Set an alarm threshold for
high battery temperatures.
The parameter is
configurable in any mode.
50°C
45–55°C
Undertem
p. thres.
Set an alarm threshold for
low battery temperatures.
The parameter is
configurable in any mode.
–5°C
–30°C to +5°C
Charge
curr. limit
Set a charge current limit.
The parameter is
configurable in any mode.
2.0 A
1.0–4.0 A
Overcurre
nt thres.
Set an alarm threshold for
battery overcurrent. The
parameter is configurable
in any mode.
6.0 A
4.0–8.0 A
Battery
string
sharing
Battery string sharing is
supported in a parallel
system.
Disable
Disabled,
Enabled
NO TE
The battery sharing setting is available only for the UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01. Battery sharing is enabled for the UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL by default.
Figure 4-36 Basic screen (UPS2000-G-6KRTS/UPS2000-G-10KRTS/UPS2000-
G-15KRTL/UPS2000-G-20KRTL)
UPS2000-G- (6 kVA-20 kVA)
User Manual
4 Control Panel
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
71