Item
Description
Defa
ult
Valu
e
Value Range
Temp.
comp.
coef.
Set a float voltage correction
coefficient based on the battery
temperature when a battery
temperature sensor is connected.
The parameter is configurable in any
mode.
3.3
mV/
(
℃
*c
ell)
0.0–6.0 mV/
(
℃
*cell)
●
Discharge screen
Figure 4-40 Discharge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Table 4-30 Discharge screen (UPS2000-G-15KRTL-01/UPS2000-G-20KRTL-01)
Item
Description
Defa
ult
Valu
e
Value Range
Max.
time
Set the maximum discharge
time. When the discharge time
reaches the value, the UPS
powers off. If you set the value
to 0Hour, the discharge time is
not limited. The parameter is
configurable in non-battery
mode or non-battery ECO
mode.
NOTE
● If you expect the battery
discharge time to be greater
than 24 hours, set Max. time
to 0 hour. Otherwise, the
system may power off.
● If you set Max. time to 0 hour,
the battery string may remain
in the small-current discharge
state according to the
proportion of the battery
capacity to the load power,
which affects the battery
lifecycle.
16
hour
s
0–24 hours
UPS2000-G- (6 kVA-20 kVA)
User Manual
4 Control Panel
Issue 18 (2021-07-16)
Copyright © Huawei Technologies Co., Ltd.
75