Table 4-24 Other settings
Item
Description
Def
ault
Val
ue
Value
Range
Recovery
delay time
Delay time that the UPS takes in transferring
from battery mode to normal mode when the
mains recovers This parameter is
configurable only after the inverter is shut
down.
NOTE
If Recovery delay time(s) is set to 0S, the actual
recovery delay time is 1 second.
5s
0–900s
Maximum
bypass
transfer
times
Maximum number of bypass transfers within
30 minutes When the number of bypass
transfers exceeds this value, the UPS keeps
running in bypass mode (in ECO mode, the
UPS keeps running in inverter mode). This
parameter is configurable only after the
inverter is shut down.
NOTICE
Do not set the UPS to ECO mode when the UPS
connects to an isolated transformer.
3
1–3
Output
transform
er
If an output transformer is connected, set the
parameter to Enabled; otherwise, set it to
Disabled. This parameter is configurable
only after the inverter is shut down.
NOTE
When connecting an isolation transformer to the
system output, connect the UPS output load to the
pL terminal and disable the power segment
function.
Dis
able
d
Disable
d,
Enabled
Generator
mode
If the mains input voltage quality is good,
Weak adaptability mode is recommended. If
the mains input voltage is of average quality
(for example, a high-performance generator
or a common power grid is connected),
Balance mode is recommended. If the mains
input voltage quality is poor (for example, a
common generator is connected), Strong
adaptability mode is recommended. This
parameter is configurable only after the
inverter is shut down.
Bal
anc
e
mo
de
Weak
adaptab
ility
mode,
Balance
mode,
Strong
adaptab
ility
mode
UPS2000-G- (6 kVA-20 kVA)
User Manual
4 Control Panel
Issue 18 (2021-07-16)