Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System
Handling Suggestion
0131-01 Ambien
t
overtem
peratur
e
Minor
Automa
tic
An alarm is generated.
Possible causes:
● The ambient
temperature in the
UPS equipment room
exceeds the alarm
threshold (default
value: 40°C).
● The temperature and
humidity transducer
is faulty.
Measures:
● Check the ambient
temperature in the
UPS equipment
room.
● Replace the
temperature and
humidity transducer.
0133-01 Ambien
t
underte
mperat
ure
Minor
Possible causes:
● The ambient
temperature in the
UPS equipment room
is below the alarm
threshold (default
value: 0ºC).
● The temperature and
humidity transducer
is faulty.
Measures:
● Check the ambient
temperature in the
UPS equipment
room.
● Replace the
temperature and
humidity transducer.
UPS2000-G- (6 kVA-20 kVA)
User Manual
D Alarm Handling