Item
Specifications
Output frequency
50 Hz/60 Hz
General input
2 x 63 A/2P
UPS input
63 A/1P
Battery power distribution
125 A/2P x 2
Air conditioner power distribution
25 A/1P MCB x 2
UPS output
63 A/1P
UPS bypass
63 A/1P
Output branch
4 x 40 A/1P
Dimensions (H x W x D)
130 mm x 442 mm x 450 mm
3.2.4 (Optional) rPDU
The rPDU is a basic socket, rather than a monitoring socket.
Figure 3-3 Half-height rPDU
Table 3-4 rPDU technical specifications
Item
Specifications (Vertically Installed
Half-Height rPDU)
Rated current
32 A
Input frequency
50 Hz/60 Hz
Input port
Cord end terminal, no input cable
Output port configuration
IEC: 9 x C13 + 3 x C19
China standard: 9 x 10 A + 3 x 16 A
Rated output current
32 A
3.2.5 Lithium Battery ESM-48100B1
Lithium batteries provide backup power. When the mains is normal, the UPS
charges batteries. When the mains fails, lithium batteries supply power to the UPS.
FusionModule500 Smart Mini Data Center
User Manual
3 System Architecture
Issue 02 (2020-12-25)
Copyright © Huawei Technologies Co., Ltd.
24