6. Set Leak sensor to Enable and click Submit.
7. Set Leak sensor type to Leak sensor(Electroc) and click Submit.
Step 2 Check functions of water sensors.
Table 5-10 Function check
Check Method
Normal Connection Status
Alarm Clearance Method
Immerse the two
contacts of the
electrode water
sensor in water.
Leak DI alarm is generated
on the active alarm screen of
the app or on the WebUI.
Wipe dry the two contacts of
the water sensor. The alarm
disappears automatically.
----End
5.3.9 Commissioning a Cabinet Electronic Clasp Lock
Prerequisites
The cabinet door can be opened and closed properly. If the cabinet door cannot be
opened and closed properly, adjust the position of the cabinet electronic clasp lock
by performing steps 1 and 2.
Procedure
Step 1 (Optional) Check whether the cabinet door lock is leveled to 2000 (+3) mm. If
not, adjust it.
Step 2 (Optional) If the cabinet door still cannot be opened after step 1 is performed,
adjust the position of the cabinet electronic clasp lock by using the slotted holes
until the cabinet door can be opened and closed properly.
Step 3 Set device addresses for cabinet electronic clasp locks.
●
A cabinet electronic clasp lock is installed at the front and rear doors of the
cabinet respectively. The address for the cabinet electronic clasp lock on the
front door is an odd number, and that for the cabinet electronic clasp lock on
the rear door is an even number.
●
Set a device address for a cabinet electronic clasp lock by operating the toggle
switch on the cabinet electronic clasp lock. Toggle switches 1 to 6 specify the
device address in binary mode. ON indicates 1, and OFF indicates 0.
FusionModule500 Smart Mini Data Center
User Manual
5 Power-On Commissioning
Issue 02 (2020-12-25)
Copyright © Huawei Technologies Co., Ltd.
176