Maintenance
Area
Maintenance
Item
Operation
Expected Result Troubleshootin
g
UPS
Operating
environment
-
● Ambient
temperature:
0–40°C
● Humidity:
0%–95% RH
(non-
condensing)
● If the
temperature
or humidity
is abnormal,
check the
smart
cooling
product
status.
● If the input
voltage is
abnormal,
check the
power grid
status and
input cable
connection.
Liquid crystal
display (LCD)
-
According to the
status icons on
the LCD, all units
are operating
properly. No
fault or alarm
information is
found in the
active and
historical alarm
records.
If an alarm is
present, rectify
the fault by
checking the
device status
and parameters.
Lithium battery
Battery
management
alarm
-
No battery
management
alarm is
generated.
Identify the
cause of an
alarm based on
the alarm
information.
FusionModule500 Smart Mini Data Center
User Manual
6 O&M
Issue 02 (2020-12-25)
Copyright © Huawei Technologies Co., Ltd.
235