CS875-575-375-275-175 Installers Manual with CS5500 keypad
B.2.3
2.2.3 Editing a zone type
A zone type is a collection of characteristics. All the zones included in a particular zone type share the same
characteristics. Each zone must belong to a zone type. There are 20 pre-defined zone types which you can edit. To
edit a zone type, you must enable the advanced menu. The following example edits a burglary zone type so that
the input type is 24-hour and it can be automatically bypassed after five alarms within one arm period.
1.
Ensure the advanced menu is enabled. See chapter 20 for more information.
2.
Navigate with the
µ¶
keys to
Control Panel>Inputs>Zone Types
and press
OK
.
3.
Select
Burglary>Input Type>24-hour>Yes
and press
OK
.
4.
The keypad beeps once to confirm the change and returns to
24-hour
.
5.
Scroll to
Attributes>Swinger Shutdown>Yes
and press
OK
.
6.
The keypad beeps once to confirm the change and returns to Sw
inger Shutdown
.
7.
Set the value of
Inputs>Swinger Shutdown
to 5. For more information see
Setting swinger shutdown
below.
2.2.4 Setting swinger shutdown
Swinger shutdown allows the selected zone to be automatically bypassed after a specified number of alarms. To
configure swinger shutdown, you must enable the advanced menu. The following example sets swinger shutdown
to 5. This means that any zone for which swinger shutdown is enabled can be activated five times within one arm
period before it is automatically bypassed.
1.
Ensure the advanced menu is enabled. See chapter 20 for more information.
2.
Navigate with the
µ¶
keys to
Control Panel>Inputs>Swinger Shutdown
and press
OK
.
3.
Enter
5
and press
OK
.
4.
The keypad beeps once to confirm the change and returns to
Swinger Shutdown
.