CS875-575-375-275-175 Installers Manual with CS5500 keypad
B.2.15
2.1.3.1.1.7
Interior
A zone type within the building that is bypassed when the system is armed in
stay mode.
2.1.3.1.1.8
Entry Guard
A zone type that reduces false alarms. If an armed entry guard zone is
opened, the keypad sounder activates and the entry delay starts before
creating an alarm. This can be programmed as a zone type.
2.1.3.1.1.9
Final Set Door
A zone type that arms the system the moment the exit door is closed. It differs
from an exit terminator zone in that it is available in the standard CSx75 and is
attached to a zone that can also create alarms and so on.
2.1.3.1.1.10
Roller Shutter
A zone type used with roller shutter blinds. These zones can be used only on
the control panel. They cannot be used on a CS208/CS216 input expander.
2.1.3.1.1.11
B-Alarm Trip
A zone type that generates a B-alarm trip event. The event is reported to the
central station using the codes set in the B-Alarm Trip report codes menu.
Typically, all alarms are A-alarms. Both A-alarms and B-alarms activate sirens
and keypad buzzers. However, the central station reacts differently to A and B-
alarm trip events. A police patrol is sent when an A-alarm trip event is reported
(full alarm), whereas a guard from the security company is sent when a B-
alarm trip event is reported (near alarm).
If two B-alarm trip events occur within the pre-set B-alarm time, the second B-
alarm trip event is treated as an A-alarm trip event.
2.1.3.1.1.12
Trouble
A zone type that sends an alarm when the system is armed and trouble when
the system is disarmed.
2.1.3.1.2
Zone Type Name
A menu option that specifies the name of a particular zone type. This option
also allows the name to be edited.
2.1.3.1.3
Attributes
A menu entry that groups the additional characteristics of the selected zone
type.
2.1.3.1.3.1
End of Line Resistor
A zone characteristic that specifies that two 4K7 end of line resistors are used.
An end of line resistor (EOL) is a resistor that is placed on the line to stop the
signal being bounced back.
2.1.3.1.3.2
Loop Response
A zone characteristic of on-board control panel zones that specifies the
response rate. This can be either 500 ms or 50 ms.
2.1.3.1.3.3
Double Knock
A zone characteristic that causes an event only if the zone is activated twice
within a specified time. This is to prevent false alarms on PIRs.
2.1.3.1.3.4
Swinger Shutdown
A zone characteristic that allows the selected zone to be automatically
bypassed after a specified number of alarms.
An Inputs menu entry that contains the swinger count.
2.1.3.1.3.5
Bypassable
A zone characteristic that allows the zone to be bypassed.
2.1.3.1.3.6
Force Armable
A zone characteristic that allows the zone to be force armed.
2.1.3.1.3.7
Group Bypass
A zone characteristic that allows the user to bypass multiple zones with a
single operation.
2.1.3.1.3.8
Zone Inactivity Monitor
A zone characteristic that sends a report to the central station when the zone
does not change conditions within a specified time period.
2.1.3.1.3.9
Pulsed Keyswitch
A zone characteristic that allows a zone input to be used with a momentary
keyswitch. Each activation of the keyswitch toggles the armed state of the
control.
2.1.3.1.3.10
No Keypad Display
A zone characteristic that blanks the zone status when armed.
2.1.3.1.4
Sound
A menu entry that groups sounder characteristics for a particular zone type.
These characteristics determine the sounds produced by the sirens and
keypads when the selected zone is activated.
Location
Term
Definition