CS875-575-375-275-175 Installers Manual with CS5500 keypad
B.6.3
6.2.3 Wiring the CS208 / CS216 input expander
To wire the CS208 / CS216 input expander, see Table 6-2:
CS208 / CS216 input expander terminals
. Any
unused zones must have an EOL resistor across them, unless all 8 are disabled by DIP switch 6 (CS216 only).
The CS208 / CS216 input expander is similar to the CS507 output expander. A white connector J9 can be used to
connect to the CSx75 panel in a housing mounted inside the control unit.
Table 6-2: CS208 / CS216 input expander terminals
Terminal
Description
Connector on the left side
3
DATA
Connect to the KP DATA terminal of the CSx75.
AUX
Connect to the KP POS terminal of the CSx75. Current draw is 30 mA.
COM
Connect to the KP COM terminal of the CSx75.
Out
Can be used to power devices directly from the CS208 / CS216. Power comes from the
CSx75 and the current draw of these devices must be added to the total current draw of
the CS208 / CS216. The output current connected to a COM terminal is limited to 100
mA.
TAM
If not used, connect to a COM terminal.
Bottom connector
1
Z9
Connect to one side of zone 9 loop. Connect the other side to the COM terminal. Open or
short causes alarm.
COM
Common (-) terminal for zones 9 and 10.
Z10
Connect to one side of zone 10 loop. Connect the other side to the COM terminal. Open
or short causes alarm.
Z11-Z24
Connect as described for Z9 and Z10.
Additional keypad connector
4
(from top to bottom)
1
DATA
2
COM
3
Unused
4
AUX+