172
Upgrade and Maintenance Manual
BX924
S3
Main memory
8.3
Removing memory modules
8.3.1
Required tools
●
Preliminary and concluding steps: tool-less
●
Removing memory modules: tool-less
8.3.2
Preliminary steps
Before removing a memory module, perform the following steps:
Ê
Disable BitLocker functionality as described in section
"Disabling BitLocker
functionality" on page 73
.
Ê
Disable boot watchdog functionality as described in section
"Disabling boot
watchdog functionality" on page 74
.
Ê
If applicable, open the rack door as described in section
"Opening the rack
door" on page 53
.
Ê
Locate the desired server blade as described in section
"Locating the
defective server blade" on page 45
.
Ê
Shut down the defective server blade as described in section
"Shutting down
the server blade" on page 54
.
Ê
Remove the server blade from the system unit as described in section
"Removing the server blade from the system unit" on page 59
.
Ê
Open the server blade as described in section
"Opening the server blade"
on page 60
.
Ê
If applicable, remove the air cowls as described in section
"Removing the air
cowls" on page 179
.
Upgrade and Repair Units (URU)
Average hardware task duration: 15 minutes
Average software task duration: 5 minutes
Summary of Contents for PRIMERGY BX924 S3
Page 6: ...Upgrade and Maintenance Manual BX924 S3 ...
Page 16: ...16 Upgrade and Maintenance Manual BX924 S3 ...
Page 20: ...20 Upgrade and Maintenance Manual BX924 S3 Introduction ...
Page 42: ...42 Upgrade and Maintenance Manual BX924 S3 Important information ...
Page 68: ...68 Upgrade and Maintenance Manual BX924 S3 Basic hardware procedures ...
Page 104: ...104 Upgrade and Maintenance Manual BX924 S3 Basic software procedures ...
Page 180: ...180 Upgrade and Maintenance Manual BX924 S3 Main memory ...
Page 232: ...232 Upgrade and Maintenance Manual BX924 S3 Processors ...
Page 278: ...278 Upgrade and Maintenance Manual BX924 S3 System board components ...