2-13
Ch
ap. 2
M
O
UNTING
A
N
D WIRING
T
H
E IN
V
E
R
T
ER
DC reactor terminals P1 and P(+)
Connect a DC reactor (DCR) to these terminals for power factor correction.
1) Remove the jumper bar from terminals P1 and P(+).
2) Connect an optional DCR to those terminals.
• The wiring length should be 33 ft (10 m) or below.
• Do not remove the jumper bar when a DCR is not used.
• The FRN100G1S-2/4U and higher types come with a DCR. Be sure to connect the DCR.
• If a PWM converter is connected to the inverter, no DCR is required.
Be sure to connect an optional DC reactor (DCR) when the capacity of the power supply transformer exceeds 500 kVA and is
10 times or more the inverter rated capacity.
Otherwise, a fire could occur.
DC braking resistor terminals P(+) and DB (for inverters of 40 HP or below)
Capacity
(HP)
Braking transistor
Built-in DC braking
resistor (DBR)
Optional devices
Option mounting
steps required
0.5 to 15
Built-in
Built-in
External DC braking resistor
(with a larger capacity)
1), 2), 3)
20 to 40
Built-in
None
External DC braking resistor
2), 3)
For inverters of 15 HP or below, if the capacity of the built-in DC braking resistor (DBR) is insufficient since the inverter
undergoes frequent start/stop or heavy inertial load, mount an optional external DC braking resistor (DBR) with a larger capacity
to increase the braking capability, using the following steps. Before mounting the external DBR, remove the built-in DBR.
1) For inverters of 0.5 to 5 HP, disconnect the wiring of the built-in DBR from terminals P(+) and DB; for those of 7.5 to 15 HP,
disconnect the wiring from terminal DB and the internal relay terminal (see the figure below).
Insulate the terminals of the disconnected wires with insulating tape or other materials.
2) Connect an optional DBR to terminals P(+) and DB.
The internal relay terminal on inverters of 7.5 to 15 HP is left unused.
3) Arrange the DBR and inverter so that the wiring length comes to 16 ft (5 m) or less and twist the two DBR wires or route
them together in parallel.
When connecting a DC braking resistor (DBR), never connect it to terminals other than terminals P(+) and DB.
Otherwise, a fire could occur.