5-2
Ch
ap
. 5
FUNCTION C
O
DES
Drive control
The FRENIC-MEGA runs under any of the following drive controls. Some function codes apply exclusively to the specific drive
control, which is indicated by letters Y (Applicable) and N (Not applicable) in the "Drive control" column in the function code
tables given on the following pages.
Abbreviation in "Drive control" column
in function code tables
Control target (H18)
Drive control (F42)
V/f
Speed
(Frequency for V/f
and PG V/f)
V/f control
Dynamic torque vector control
PG V/f
V/f control with speed sensor
Dynamic torque vector control with speed sensor
w/o PG
Vector control without speed sensor
w/ PG
Vector control with speed sensor
Torque control
Torque
Vector control with/without speed sensor
For details about the drive control, refer to "Function code F42 (Drive Control Selection 1)."
The FRENIC-MEGA is a general-purpose inverter whose operation is customized by frequency-basis function codes,
like conventional inverters. Under the speed-basis drive control, however, the control target is a motor speed, not a
frequency, so convert the frequency to the motor speed according to the following expression.
Motor speed (r/min) = 120
×
Frequency (Hz)
÷
Number of poles
Note: Difference of notation between standard keypad and remote keypad
Descriptions in this manual are based on the standard keypad having an LCD monitor and a
five
-digit, 7-segment LED monitor (as
shown in Chapter 3). The FRENIC-MEGA also provides a remote keypad as an option, which has no LCD monitor and has a
four
-digit, 7-segment LED and a USB port.
If the standard keypad is replaced with an optional remote keypad, the display notation differs as shown below.
Function code
Name
Standard keypad (TP-G1W-J1) Remote keypad (TP-E1U)
H42
Capacitance of DC Link Bus Capacitor
Decimal notation
Hexadecimal notation
H44
Startup Counter for Motor 1
H47
Initial Capacitance of DC Link Bus Capacitor
H79
Preset Startup Count for Maintenance (M1)
A52
Startup Counter for Motor 2
b52
Startup Counter for Motor 3
r52
Startup Counter for Motor 4
d15
Feedback Input (Encoder pulse resolution)
d60
Command (Pulse Rate Input) (Encoder pulse resolution)
H43
Cumulative Run Time of Cooling Fan
By hours
On a 10-hour basis
(with the x10 LED ON)
H48
Cumulative Run Time of Capacitors on Printed Circuit
Boards
H77
Service Life of DC Link Bus Capacitor (Remaining time)
H78
Maintenance Interval (M1)
H94
Cumulative Motor Run Time 1
A51
Cumulative Motor Run Time 2
b51
Cumulative Motor Run Time 3
r51
Cumulative Motor Run Time 4
d78
Synchronous Operation (Excessive deviation detection
range)
On a 10-pulse basis
For less than 10000 pulses:
On a 10-pulse basis
For 10000 pulses or more:
On a 100-pulse basis (with
the x10 LED ON)