8-2
8.1.2 Three-phase 460 V series
LD (Low Duty)-mode inverters for light load
(0.5 to 100 HP)
Item Specifications
Type
(FRN_
_
_G1S-4U)
F50 001
002 003 005 007
010
015
020
025
030
040
050
060 075 100
Nominal applied motor
(HP)
*1
(Output rating)
0.5 1 2 3 5 7.5
10
15
20
25
30
40
50
60
75
100
Ou
tpu
t r
a
ti
ngs
Rated capacity (kVA)
*2
1.2 2.0
3.2 4.4 7.2 11
13.1
18.3
24
29
36
48
60
73 89 120
Rated voltage (V)
*3
Three-phase 380 to 480 V (with AVR function)
Rated current (A)
1.5
2.5
4
5.5
9
13.5
16.5
23
30.5
37
45
60
75
91
112
150
Overload capability
150%-1 min, 200%-3.0 s
120%-1 min
In
pu
t po
w
e
r Voltage, frequency
380 to 480 V, 50/60 Hz
Allowable
voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*4
, Frequency: +5 to -5%
Required capacity
(with DCR) (kVA)
*5
0.6 1.2
2.2 3.1 5.2 7.4 10 15 20 25 29 40 48 58
71
96
Braki
n
g
Torque (%)
*6
150%
100%
70%
15%
7 to 12%
Braking transistor
Built-in
–
Built-in braking resistor
Built-in
–
Braking time (s)
5 s
3.7 s
3.4 s
–
Duty
cycle
(%ED) 5 3 5 3 2
2.2 1.4
–
DC reactor (DCR)
Option
Standard
*7
Applicable safety
standards
UL508C, C22.2 No.14, EN61800-5-1:2007
Enclosure (IEC60529)
IP20, UL open type
IP00, UL open type
Cooling method
Natural cooling
Fan cooling
Weight / Mass
lbs (kg)
3.8
(1.7)
4.4
(2.0)
5.7
(2.6)
6.0
(2.7)
6.6
(3.0)
14
(6.5)
14
(6.5)
14
(6.5)
13
(5.8)
21
(9.5)
21
(9.5)
22
(10)
55
(25)
57
(26)
68
(31)
73
(33)
(125 to 1000 HP)
Item Specifications
Type
(FRN_
_
_G1S-4U) 125 150
200 250 300 350
450
500
600
700
800
900
1000
Nominal applied motor
(HP)
*1
(Output rating)
125 150
200 250 300 350
450
500
600
700
800
900
1000
O
u
tput r
a
ti
ngs
Rated capacity (kVA)
*2
140 167
202 242 300 331
414
518
590
669
765
932
1092
Rated voltage (V)
*3
Three-phase 380 to 480 V (with AVR function)
Rated
current
(A)
176 210
253 304 377 415
520
650
740
840
960
1170 1370
Overload capability
120%-1 min
In
pu
t powe
r Voltage, frequency
380 to 440 V, 50 Hz
380 to 480 V, 60 Hz
Allowable
voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*4
, Frequency: +5 to -5%
Required capacity
(with DCR) (kVA)
*5
114 140
165 199 248 271
347
436
489
547
611
773
871
Brak
ing
Torque (%)
*6
7
to
12%
Braking transistor
–
Built-in braking resistor –
Braking time (s)
–
Duty cycle (%ED)
–
DC reactor (DCR)
Standard
*7
Applicable safety
standards
UL508C, C22.2 No.14, EN61800-5-1:2007
Enclosure (IEC60529)
IP00, UL open type
Cooling method
Fan cooling
Weight / Mass
lbs (kg)
93
(42)
137
(62)
141
(64)
207
(94)
216
(98)
284
(129)
309
(140)
540
(245)
540
(245)
728
(330)
728
(330)
1169
(530)
1169
(530)
*1 US-4P standard induction motor
*2 Rated capacity is calculated assuming the rated output voltage as 230 V for 230 V series and 460 V for 460 V series.
*3 Output voltage cannot exceed the power supply voltage.
*
4
3)
-
61800
(IEC
67
×
(V)
voltage
average
phase
-
Three
(V)
voltage
Min.
-
(V)
voltage
Max.
(%)
unbalance
Voltage
=
If this value is 2 to 3%, use an optional AC reactor (ACR).
*5 Required when a DC reactor (DCR) is used.
*6 Average braking torque for the motor running alone, without external braking resistor. (It varies with the efficiency of the motor.)
*7 The FRN100G1S-4U or higher type comes with a DC reactor (DCR).