5-63
F29 to F31
F32, F34,
F35
Analog Output [FM1] and [FM2] (Mode selection, Voltage adjustment, Function)
These function codes allow terminals [FM1] and [FM2] to output monitored data such as the output frequency and the
output current in an analog DC voltage or current. The magnitude of such analog voltage or current is adjustable.
Mode selection (F29 and F32)
F29 and F32 specify the property of the output to terminals [FM1] and [FM2], respectively. You need to set the slide
switches on the control printed circuit board (control PCB). Refer to Chapter 2 "Mounting and Wiring of the Inverter."
Terminal [FM1]
Terminal [FM2]
Data for F29
Position of slide switch
SW4 on the control PCB
Data for F32
Position of slide switch
SW6 on the control PCB
Voltage (0 to +10 VDC)
0
VO1
0
VO2
Current (4 to +20 mA DC)
1
IO1
1
IO2
The output current is not isolated from analog input, and does not have an isolated power supply. Therefore, if an
electrical potential relationship between the inverter and peripheral equipment has been established, e.g., by
connecting an analog, cascade connection of a current output device is not available.
Keep the connection wire length as short as possible.
Voltage adjustment (F30 and F34)
F30 allows you to adjust the output voltage within the range of 0 to 300%.
Function (F31 and F35)
F31 and F35 specify what is output to analog output terminals [FM1] and [FM2], respectively.
Data for
F31/F35
[FM1]/[FM2] output
Function
(Monitor the following)
Meter scale
(Full scale at 100%)
0
Output frequency 1
(before slip compensation)
Output frequency of the inverter
(Equivalent to the motor synchronous
speed)
Maximum frequency (F03)
1
Output frequency 2
(after slip compensation)
Output frequency of the inverter
Maximum frequency (F03)
2
Output current
Output current (RMS) of the inverter
Twice the inverter rated current
3
Output voltage
Output voltage (RMS) of the inverter
250 V for 230 V series,
500 V for 460 V series
4
Output torque
Motor shaft torque
Twice the rated motor torque
5 Load
factor
Load factor
(Equivalent to the indication of the load
meter)
Twice the rated motor load
6
Input power
Input power of the inverter
Twice the rated output of the inverter
7
PID feedback amount (PV) Feedback amount under PID control
100% of the feedback amount
8
PG feedback value (speed)
Speed detected through the PG interface,
or estimated speed under vector control
without speed sensor
Maximum speed as 100%
9
DC link bus voltage
DC link bus voltage of the inverter
500 V for 230 V series,
1000 V for 460 V series
Output form