5-15
Code Name
Data
setting
range
Cha
nge w
hen
ru
nnin
g
Da
ta
cop
yi
ng Default
setting
Drive control
Refer
to
page:
V/f
PG
V/f
w/o
PG
w/
PG
Torque
control
H73 Torque Limiter
(Operating
conditions)
0: Enable during ACC/DEC and running at constant
speed
1: Disable during ACC/DEC and enable during running at
constant speed
2: Enable during ACC/DEC and disable during running at
constant speed
N Y
0 Y Y Y
Y Y 5-66
5-129
H74
(Control target) 0: Motor-generating torque limit
1: Torque current limit
2: Output power limit
N Y
1 N N
Y
Y Y
H75
(Target quadrants) 0: Drive/brake
1: Same for all four quadrants
2: Upper/lower limits
N Y
0 N N
Y
Y Y
H76
(Frequency increment limit
for
braking)
0.0 to 500.0 Hz
Y Y
5.0 Y Y
N
N N
5-128
5-129
H77 Service Life of DC Link Bus
Capacitor (Remaining
time)
0 to 87600 hours
Y N
- Y Y Y
Y Y
5-130
H78 Maintenance Interval (M1)
0: Disable; 1 to 99990 hours
Y N
87600
Y Y Y
Y Y
5-126
H79 Preset Startup Count for
Maintenance (M1)
0: Disable; 1 to 65535 times
Y N
0 Y Y Y
Y Y
5-130
H80 Output Current Fluctuation Damping
Gain for Motor 1
0.00 to 1.00
Y Y
0.20
Y Y
N
N Y
5-130
H81 Light Alarm Selection 1
0000 to FFFF (hex.)
Y Y
0000
Y Y
Y
Y Y
H82 Light Alarm Selection 2
0000 to FFFF (hex.)
Y Y
0000
Y Y
Y
Y Y
H84 Pre-excitation
(Initial level) 100% to 400%
Y Y
100
N N Y Y Y 5-133
H85
(Time) 0.00: Disable; 0.01 to 30.00 s
Y Y
0.00
N N
Y
Y Y
H86 Reserved *
9
―
- - - - -
-
- -
5-134
H87 Reserved *
9
―
- - - - -
-
- -
H88 Reserved *
9
―
- - - - -
-
- -
H89 Reserved *
9
―
- - - - -
-
- -
H90 Reserved *
9
―
- - - - -
-
- -
H91 PID Feedback Wire Break Detection 0.0: Disable alarm detection
0.1 to 60.0 s
Y Y
0.0 Y Y
Y
Y N
5-134
H92 Continuity of Running
(P) 0.000 to 10.000 times; 999
Y Y1Y2
999
Y Y N N N 5-51
H93
(I) 0.010 to 10.000 s; 999
Y Y1Y2
999
Y Y N N N 5-134
H94 Cumulative Motor Run Time 1
0 to 99990 hours
(The cumulative run time can be modified or reset.)
N N
- Y Y Y
Y Y 5-126
5-134
H95 DC Braking
(Braking
response
mode)
0: Slow
1: Quick
Y Y
1 Y Y
N
N N 5-58
5-134
H96 STOP Key Priority/
Start Check Function
Data STOP key priority
Start check function
0:
Disable
Disable
1:
Enable
Disable
2:
Disable
Enable
3:
Enable
Enable
Y Y
3 Y Y
Y
Y Y
5-134
H97 Clear Alarm Data
0: Disable
1: Enable (Setting "1" clears alarm data and then returns
to "0.")
Y N
0 Y Y Y
Y Y
H98 Protection/Maintenance Function
(Mode
selection)
0 to 255: Display data in decimal format
Bit 0: Lower the carrier frequency automatically
(0: Disabled; 1: Enabled)
Bit 1: Detect input phase loss
(0: Disabled; 1: Enabled)
Bit 2: Detect output phase loss (0: Disabled; 1: Enabled)
Bit 3: Select life judgment threshold of DC link bus
capacitor
(0: Factory default level; 1: User setup level)
Bit 4: Judge the life of DC link bus capacitor
(0: Disabled; 1: Enabled)
Bit 5: Detect DC fan lock
(0: Enabled; 1: Disabled)
Bit 6: Detect braking transistor error (for 40 HP or below)
(0: Disabled; 1: Enabled)
Bit 7: Switch IP20/IP40 enclosure
(0: IP20; 1: IP40)
Y Y
83 Y Y
Y
Y Y
5-135
*9 Factory use. Do not access these function codes.