5-139
Table 5.5 Function Codes to be Switched (Continued)
Name
Function code
Object of
parameter
switching
1st
motor
2nd
motor
3rd
motor
4th
motor
Speed control
(Speed command filter)
d01
A43
b43
r43
Y
(Speed detection filter)
d02
A44
b44
r44
Y
P (Gain)
d03
A45
b45
r45
Y
I (Integral time)
d04
A46
b46
r46
Y
(Output filter)
d06
A48
b48
r48
Y
(Notch filter resonance frequency)
d07
A49
b49
r49
(Notch filter attenuation level)
d08
A50
b50
r50
Cumulative motor run time
H94
A51
b51
r51
Startup counter for motor
H44
A52
b52 r52
Motor
(%X correction factor 1)
P53
A53
b53
r53
(%X correction factor 2)
P54
A54
b54
r54
(Torque current under vector control)
P55
A55
b55
r55
(Induced voltage factor under vector control)
P56
A56
b56
r56
Reserved for particular manufacturers
d51
d52
d53
d54
P57
A57
b57 r57
Table 5.6 Function Codes Unavailable for the 2nd to 4th Motors
Name
Function codes
Operation in 2nd to 4th motors
Non-linear V/f pattern
H50 to H53, H65, H66
Disabled
Starting frequency 1 (Holding time)
F24
Disabled
Stop frequency (Holding time)
F39
Disabled
Overload early warning/Current detection
E34, E35
Disabled
Droop control
H28
Disabled
UP/DOWN
control
(Initial frequency setting)
H61
Fixed at the initial setting (0 Hz)
PID control
J01 to J06, J08 to J13, J15 to J19,
J56 to J62, E40, E41, H91
Disabled
Dew condensation prevention
J21, F21, F22
Disabled
Brake signal
J68 to J72, J95, J96
Disabled
Current limiter
F43, F44
Disabled
Rotational direction limitation
H08
Disabled
Pre-excitation H84,
H85
Disabled
Maintenance Interval/ Preset Startup Count
for Maintenance
H78, H79
Disabled
NTC thermistor
H26, H27
Disabled
ASR Switching Time (d25)
Data setting range: 0.000 to 1.000 (s)
Parameter switching is possible even during operation. For example, speed control P (Gain) and I (Integral time) listed in
Table 5.5 can be switched.
Switching these parameters during operation may cause an abrupt change of torque and result in a mechanical shock,
depending on the driving condition of the load.
To reduce such a mechanical shock, the inverter decreases the abrupt torque change using the ramp function of ASR
Switching Time (d25).