![Fuji Electric FRENIC-MEGA Instruction Manual Download Page 136](http://html1.mh-extra.com/html/fuji-electric/frenic-mega/frenic-mega_instruction-manual_2341853136.webp)
5-17
Code
Name
Data setting range
Ch
an
ge
wh
e
n
ru
nning
Dat
a
cop
yi
ng
Default
setting
Drive control
Refer
to
page:
V/f
PG
V/f
w/o
PG
w/
PG
Torque
control
A18 Motor 2
(Auto-tuning) 0: Disable
1: Tune while the motor stops. (%R1, %X and rated slip
frequency)
2: Tune while the motor is rotating under V/f control
(%R1, %X, rated slip frequency, no-load current,
magnetic saturation factors 1 to 5, and magnetic
saturation extension factors "a" to "c")
3: Tune while the motor is rotating under vector control
(%R1, %X, rated slip frequency, no-load current,
magnetic saturation factors 1 to 5, and magnetic
saturation extension factors "a" to "c." Available when
the vector control is enabled.
N N 0 Y
Y
Y
Y Y
―
A19
(Online tuning) 0: Disable 1: Enable
Y Y 0 Y
N
N
N N
A20
(No-load current) 0.00 to 2000 A
N Y1
Y2
*7 Y Y Y Y Y
A21
(%R1) 0.00% to 50.00%
Y Y1
Y2
*7 Y Y Y Y Y
A22
(%X) 0.00% to 50.00%
Y Y1
Y2
*7 Y Y Y Y Y
A23 (Slip compensation gain for driving) 0.0% to 200.0%
Y*
Y 100.0
Y Y Y Y N
A24 (Slip compensation response time) 0.01 to 10.00s
Y Y1
Y2 0.12
Y Y N N N
A25 (Slip compensation gain for braking) 0.0% to 200.0%
Y*
Y 100.0
Y Y Y Y N
A26
(Rated slip frequency) 0.00 to 15.00 Hz
N Y1
Y2
*7 Y Y Y Y N
A27
(Iron loss factor 1) 0.00% to 20.00%
Y Y1
Y2
*7 Y Y Y Y Y
A28
(Iron loss factor 2) 0.00% to 20.00%
Y Y1
Y2 0.00
Y Y Y Y Y
A29
(Iron loss factor 3) 0.00% to 20.00%
Y Y1
Y2 0.00
Y Y Y Y Y
A30
(Magnetic saturation factor 1) 0.0% to 300.0%
Y Y1
Y2
*7 Y Y Y Y Y
A31
(Magnetic saturation factor 2) 0.0% to 300.0%
Y Y1
Y2
*7 Y Y Y Y Y
A32
(Magnetic saturation factor 3) 0.0% to 300.0%
Y Y1
Y2
*7 Y Y Y Y Y
A33
(Magnetic saturation factor 4) 0.0% to 300.0%
Y Y1
Y2
*7 Y Y Y Y Y
A34
(Magnetic saturation factor 5) 0.0% to 300.0%
Y Y1
Y2
*7 Y Y Y Y Y
A35
(Magnetic saturation extension
factor
"a")
0.0% to 300.0%
Y Y1
Y2
*7 Y Y Y Y Y
A36
(Magnetic saturation extension
factor
"b")
0.0% to 300.0%
Y Y1
Y2
*7 Y Y Y Y Y
A37
(Magnetic saturation extension
factor
"c")
0.0% to 300.0%
Y Y1
Y2
*7 Y Y Y Y Y
A39 Motor 2 Selection
0: Motor characteristics 0 (Fuji standard motors, 8-series)
1: Motor characteristics 1 (HP rating motors)
2: Motor characteristics 2 (Fuji motors exclusively designed
for vector control)
3: Motor characteristics 3 (Fuji standard motors, 6-series)
4: Other motors
N Y1
Y2
1 Y Y Y Y Y
A40 Slip Compensation 2
(Operating
conditions)
0: Enable during ACC/DEC and at base frequency or
above
1: Disable during ACC/DEC and enable at base frequency
or above
2: Enable during ACC/DEC and disable at base frequency
or above
3: Disable during ACC/DEC and at base frequency or
above
N Y 0 Y
Y
N
N N
A41 Output Current Fluctuation Damping
Gain for Motor 2
0.00 to 1.00
Y Y 0.20
Y
Y
N
N N
A42 Motor/Parameter Switching 2
(Mode
selection)
0: Motor (Switch to the 2nd motor)
1: Parameter (Switch to particular A codes)
N Y 0 Y
Y
Y
Y Y 5-137
A43 Speed Control 2
(Speed command filter)
0.000 to 5.000 s
Y Y 0.020
N Y Y Y N
―
A44
(Speed detection filter) 0.000 to 0.100 s
Y*
Y 0.005
N Y Y Y N
A45
P (Gain) 0.1 to 200.0 times
Y*
Y 10.0
N Y Y Y N
A46
I (Integral time) 0.001 to 9.999 s
Y*
Y 0.100
N Y Y Y N
A48
(Output filter) 0.000 to 0.100 s
Y Y 0.002
N Y Y Y N
A49 (Notch filter resonance frequency) 1 to 200 Hz
Y Y 200
N
N
N
Y N
A50
(Notch filter attenuation level) 0 to 20 dB
Y Y 0 N
N
N
Y N
A51 Cumulative Motor Run Time 2
0 to 99990 hours
(The cumulative run time can be modified or reset.)
N N - Y
Y
Y
Y Y
A52 Startup Counter for Motor 2
Indication of cumulative startup count
0 to 65535 times
Y N - Y
Y
Y
Y Y
A53 Motor 2
(%X correction factor 1) 0% to 300%
Y Y1
Y2
100
Y Y Y Y Y
A54
(%X correction factor 2) 0% to 300%
Y Y1
Y2
100
Y Y Y Y Y
A55 (Torque current under vector control) 0.00 to 2000 A
N Y1
Y2
*7 N N Y Y Y
A56
(Induced voltage factor under
vector
control)
50 to 100
N Y1
Y2 85
(90)
*8
N N Y Y Y
A57 Reserved *
9
―
- - - -
-
-
- -
*7 The motor parameters are automatically set, depending upon the inverter's capacity. See Table B.
*8 85% for inverters of 150 HP or less; 90% for those of 175 HP or above.
*9 Factory use. Do not access these function codes.
Summary of Contents for FRENIC-MEGA