5-80
Ch
ap
. 5
FUNCTION C
O
DES
E codes
Function code data
Terminal commands assigned
Symbol
Drive control
Related
function codes
Active ON Active OFF
V/f PG
V/f
w/o
PG
w/
PG
Torque
control
26 1026
Enable auto search for idling motor
speed at starting
STM
Y
Y
Y
N
Y
H09, d67
1030 30
Force
to
stop
STOP
Y
Y
Y
Y
Y
F07, H56
32 1032
Pre-excitation
EXITE
N
N
Y
Y
N
H84, H85
33 1033
Reset PID integral and differential
components
PID-RST
Y
Y
Y
Y
N
J01 to J19,
J56 to J62
34 1034
Hold
PID
integral
component
PID-HLD
Y
Y
Y
Y
N
35
1035
Select local (keypad) operation
LOC
Y
Y
Y
Y
Y
(See Section
4.2.2.)
36
1036
Select motor 3
M3
Y
Y
Y
Y Y A42,
b42
37
1037
Select motor 4
M4
Y
Y
Y
Y
Y
A42, r42
39
⎯
Protect motor from dew condensation
DWP
Y
Y
Y
Y
Y
J21
40
⎯
Enable integrated sequence to switch to
commercial power (50 Hz)
ISW50
Y
Y
N
N
N
J22
41
⎯
Enable integrated sequence to switch to
commercial power (60 Hz)
ISW60
Y
Y
N
N
N
47 1047
Servo-lock
command
LOCK
N
N
N
Y
N
J97 to J99
48
⎯
Pulse train input
(available only on terminal [X7])
PIN
Y
Y
Y
Y
Y
F01, C30,
d62, d63
49 1049
Pulse train sign
(available on terminals except [X7])
SIGN
Y
Y
Y
Y
Y
70
1070
Cancel constant peripheral speed control
Hz/LSC
Y
Y
Y
Y
N
d41
71 1071
Hold the constant peripheral speed
control frequency in the memory
LSC-HLD
Y
Y
Y
Y
N
72 1072
Count the run time of commercial
power-driven motor 1
CRUN-M1
Y
Y
N
N
Y
H44, H94
73 1073
Count the run time of commercial
power-driven motor 2
CRUN-M2
Y
Y
N
N
Y
74 1074
Count the run time of commercial
power-driven motor 3
CRUN-M3
Y
Y
N
N
Y
75 1075
Count the run time of commercial
power-driven motor 4
CRUN-M4
Y
Y
N
N
Y
76 1076
Select
droop
control
DROOP
Y
Y
Y
Y
N
H28
77
1077
Cancel PG alarm
PG-CCL
N
Y
N
Y
Y
⎯
80
1080
Cancel customizable logic
CLC
Y
Y
Y
Y
Y
E01 to E07,
U81 to U85
81
1081
Clear all customizable logic timers
CLTC
Y
Y
Y
Y
Y
98
⎯
Run forward
(Exclusively assigned to [FWD] and
[REV] terminals by E98 and E99)
FWD
Y
Y
Y
Y
Y
F02
99
⎯
Run reverse
(Exclusively assigned to [FWD] and
[REV] terminals by E98 and E99)
REV
Y
Y
Y
Y
Y
100
⎯
No function assigned
NONE
Y
Y
Y
Y
Y
U81 to U85
Some negative logic (Active OFF) commands cannot be assigned to the functions marked with "
⎯
" in the "Active
OFF" column.
The "Enable external alarm trip" (data = 1009) and "Force to stop" (data = 1030) are fail-safe terminal commands.
In the case of "Enable external alarm trip," when data = 1009, "Active ON" (alarm is triggered when ON); when
data = 9, "Active OFF" (alarm is triggered when OFF).