E codes
E46
LCD Monitor (Language selection)
E46 specifies the language to display on the keypad (TP-G1W-J1) as follows:
Data for E46
Language
0 Japanese
1 English
2 German
3 French
4 Spanish
5 Italian
E47
LCD Monitor (Contrast control)
E47 adjusts the contrast of the LCD monitor on the keypad as follows:
Data for E47
0, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10
Contrast Low
High
E48
LED Monitor (Speed monitor item)
(Refer to E43.)
E50
Coefficient for Speed Indication
E50 specifies the coefficient that is used when the load shaft speed or line speed is displayed on the LED monitor. (Refer to
the description of E43.)
Load shaft speed (r/min) = (E50: Coefficient for speed indication)
×
(Output frequency Hz)
Line speed (m/min)
= (E50: Coefficient for speed indication)
×
(Output frequency Hz)
- Data setting range: 0.01 to 200.00
E51
Display Coefficient for Input Watt-hour Data
E51 specifies a display coefficient (multiplication factor) for displaying the input watt-hour data (
5_10
) in a part of
maintenance information on the keypad.
Input watt-hour data = Display coefficient (E51 data)
×
Input watt-hour (kWh)
- Data setting range: 0.000 (cancel/reset); 0.001 to 9999
Setting E51 data to 0.000 clears the input watt-hour and its data to "0." After clearing, be sure to restore E51 data to
the previous value; otherwise, input watt-hour data will not be accumulated.
E52
Keypad (Menu display mode)
E52 provides a choice of three menu display modes for the remote keypad TP-E1U (option) as listed below.
Data for E52
Menu display mode
Menus to be displayed
0
Function code data editing mode
Menus #0, #1 and #7
1
Function code data check mode
Menus #2 and #7
2
Full-menu mode
Menus #0 through #7