![Fuji Electric FRENIC-MEGA Instruction Manual Download Page 209](http://html1.mh-extra.com/html/fuji-electric/frenic-mega/frenic-mega_instruction-manual_2341853209.webp)
5-90
Ch
ap
. 5
FUNCTION C
O
DES
E codes
3) Sequence with an emergency switching function --Part 2 (Automatic switching by the alarm output issued by the
inverter)
Cancel PG alarm--
PG-CCL
(Function code data = 77)
When this terminal command is ON, the PG wire break alarm is ignored. Use this terminal command when switching PG
wires for switching motors, for example, to prevent it from being detected as PG wire break.
Run forward --
FWD
(Function code data = 98)
Turning this terminal command ON runs the motor in the forward direction; turning it OFF decelerates it to stop.
This terminal command can be assigned only by E98 or E99.
Run reverse --
REV
(Function code data = 99)
Turning this terminal command ON runs the motor in the reverse direction; turning it OFF decelerates it to stop.
This terminal command can be assigned only by E98 or E99
E10 to E15 Acceleration Time 2 to 4, Deceleration Time 2 to 4
(Refer to F07.)
E16, E17
Torque Limiter 2-1, 2-2
(Refer to F40.)
Summary of Contents for FRENIC-MEGA
Page 36: ...2 6 Unit inch mm Refer to Section 2 3 3 9...
Page 356: ...MEMO...