FUNCTION C
O
DES
H30
Communications Link Function (Mode selection)
y98 (Bus Link Function, Mode selection)
Using the RS-485 communications link (standard/option) or fieldbus (option) allows you to issue frequency commands and
run commands from a computer or PLC at a remote location, as well as monitor the inverter running information and the
function code data.
H30 and y98 specify the sources of those commands--"inverter itself" or "computers or PLCs via the RS-485
communications link or fieldbus." H30 is for the RS-485 communications link; y98 for the fieldbus.
Command sources selectable
Command sources
Description
Inverter itself
Sources except RS-485 communications link and fieldbus
Frequency command source: Specified by F01/C30, or multi-frequency command
Run command source: Via the keypad or digital input terminals selected by F02
RS-485 communications link
(port 1)
Via the standard RJ-45 port used for connecting a keypad
RS-485 communications link
(port 2)
Via the terminals DX+, DX- and SD on the control PCB
Fieldbus (option)
Via fieldbus (option) using FA protocol such as DeviceNet or PROFIBUS-DP
Command sources specified by H30 (Communications link function, Mode selection)
Data for H30
Frequency command
Run command
0
Inverter itself (F01/C30)
Inverter itself (F02)
1
RS-485 communications link (port 1)
Inverter itself (F02)
2
Inverter itself (F01/C30)
RS-485 communications link (port 1)
3
RS-485 communications link (port 1)
RS-485 communications link (port 1)
4
RS-485 communications link (port 2)
Inverter itself (F02)
5
RS-485 communications link (port 2)
RS-485 communications link (port 1)
6
Inverter itself (F01/C30)
RS-485 communications link (port 2)
7
RS-485 communications link (port 1)
RS-485 communications link (port 2)
8
RS-485 communications link (port 2)
RS-485 communications link (port 2)
Command sources specified by y98 (Bus link function, Mode selection)
Data for y98
Frequency command
Run command
0
Follow H30 data
Follow H30 data
1
Via fieldbus (option)
Follow H30 data
2
Follow H30 data
Via fieldbus (option)
3
Via fieldbus (option)
Via fieldbus (option)