![Fuji Electric FRENIC-MEGA Instruction Manual Download Page 149](http://html1.mh-extra.com/html/fuji-electric/frenic-mega/frenic-mega_instruction-manual_2341853149.webp)
5-30
Ch
ap
. 5
FUNCTION C
O
DES
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
y codes: LINK Functions
Code Name
Data
setting
range
Ch
an
ge
wh
e
n
run
ni
ng
Data c
op
yin
g
Default
setting
Drive control
Refer
to
page:
V/f
PG
V/f
w/o
PG
w/
PG
Torque
control
y01 RS-485 Communication 1
(Station
address)
1 to 255
N Y 1 Y
Y
Y
Y Y
5-176
y02 (Communications error processing) 0: Immediately trip with alarm
er8
1: Trip with alarm
er8
after running for the period specified
by timer y03
2: Retry during the period specified by timer y03. If the retry
fails, trip with alarm
er8
.
If it succeeds, continue to run.
3: Continue to run
Y Y 0 Y
Y
Y
Y Y
y03
(Timer) 0.0 to 60.0 s
Y Y 2.0 Y
Y
Y
Y Y
y04
(Baud rate) 0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
Y Y 3 Y
Y
Y
Y Y
y05
(Data length) 0: 8 bits
1: 7 bits
Y Y 0 Y
Y
Y
Y Y
y06
(Parity check) 0: None (2 stop bits)
1: Even parity (1 stop bit)
2: Odd parity (1 stop bit)
3: None (1 stop bit)
Y Y 0 Y
Y
Y
Y Y
y07
(Stop bits) 0: 2 bits
1: 1 bit
Y Y 0 Y
Y
Y
Y Y
y08 RS-485 Communication 1
(No-response error detection time)
0: No detection; 1 to 60 s
Y Y 0 Y
Y
Y
Y Y
y09
(Response interval) 0.00 to 1.00 s
Y Y 0.01
Y
Y
Y
Y Y
y10
(Protocol selection) 0: Modbus RTU protocol
1: FRENIC Loader protocol (SX protocol)
2: Fuji general-purpose inverter protocol
Y Y 1 Y
Y
Y
Y Y
y11 RS-485 Communication 2
(Station
address)
1 to 255
N Y 1 Y
Y
Y
Y Y
y12 (Communications error processing) 0: Immediately trip with alarm
erp
1: Trip with alarm
erp
after running for the period specified
by timer y13
2: Retry during the period specified by timer y13. If the retry
fails, trip with alarm
erp
. If it succeeds, continue to
run.
3: Continue to run
Y Y 0 Y
Y
Y
Y Y
y13
(Timer) 0.0 to 60.0 s
Y Y 2.0 Y
Y
Y
Y Y
y14
(Baud rate) 0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
Y Y 3 Y
Y
Y
Y Y
y15
(Data length) 0: 8 bits
1: 7 bits
Y Y 0 Y
Y
Y
Y Y
y16
(Parity check) 0: None (2 stop bits)
1: Even parity (1 stop bit)
2: Odd parity (1 stop bit)
3: None (1 stop bit)
Y Y 0 Y
Y
Y
Y Y
y17
(Stop bits) 0: 2 bits
1: 1 bit
Y Y 0 Y
Y
Y
Y Y
y18 (No-response error detection time) 0: No detection; 1 to 60 s
Y Y 0 Y
Y
Y
Y Y
y19
(Response interval) 0.00 to 1.00 s
Y Y 0.01
Y
Y
Y
Y Y
y20
(Protocol selection) 0: Modbus RTU protocol
2: Fuji general-purpose inverter protocol
Y Y 0 Y
Y
Y
Y Y
y97 Communication Data Storage
Selection
0: Save into nonvolatile storage (Rewritable times limited)
1: Write into temporary storage (Rewritable times unlimited)
2: Save all data from temporary storage to nonvolatile one
(After saving data, the y97 data automatically returns to
"1.")
Y Y 0 Y
Y
Y
Y Y
5-179
y98 Bus Link Function (Mode selection) Frequency command
Run command
0: Follow H30 data
Follow H30 data
1: Via fieldbus option
Follow H30 data
2: Follow H30 data
Via fieldbus option
3: Via fieldbus option
Via fieldbus option
Y Y 0 Y
Y
Y
Y Y
5-124
5-179
y99 Loader Link Function
(Mode
selection)
Frequency command
Run command
0: Follow H30 and y98 data
Follow H30 and y98 data
1: Via RS-485 link
Follow H30 and y98 data
(FRENIC Loader)
2: Follow H30 and y98 data
Via RS-485 link
(FRENIC
Loader)
3: Via RS-485 link
Via RS-485 link
(FRENIC Loader)
(FRENIC Loader)
Y N 0 Y
Y
Y
Y Y
5-179