Device Functions Proline Promag 55 FOUNDATION Fieldbus
6 Block TOTALIZER
Hauser
39
6.2
Group HANDLING TOTALIZER
TOTALIZER
D
⇒
TOTALIZER 1
DAA
⇓
TOTALIZER 2
DAB
⇓
TOTALIZER 3
DAC
⇓
HANDLING TOTALIZER
DJA
⇒
Handling totalizer functions
Function description
TOTALIZER
→
HANDLING TOTALIZER
→
Handling totalizer functions
RESET ALL TOTALIZERS
(3800)
Use this function to reset the totals (including all overflows) of the Totalizers (1 to 3) to
zero (= RESET).
Options:
NO
YES
Factory setting:
NO
FAILSAFE ALL TOT
(3801)
Use this function to define the common response of all Totalizers (1 to 3) in case of error.
Options:
STOP
The totalizer is paused until the fault is rectified.
ACTUAL VALUE
The totalizers continue to count based on the actual flow measured value. The fault is
ignored .
HOLD VALUE
The totalizers continue to count the flow based on the last valid flow value (before the
fault occurred).
Factory setting:
STOP