3 Transducer Block
Device functions Proline Promag 55 FOUNDATION Fieldbus
102
Hauser
Add. Line Mux -
100%-Value
AUTO - OOS
!
Note!
The entry is not active unless one of the following was selected in the
parameter "Add. Line Mux - Assign":
• MASS FLOW IN %
• VOLUME FLOW IN %
• MASS FLOW BARGRAPH IN %
• VOLUME FLOW BARGRAPH IN %
Use this parameter to define the flow value to be shown on the display as
the 100% value.
User input:
5-digit floating-point number
Factory setting:
Nominal diameter and country dependent
!
Note!
The unit is taken from the corresponding system unit ("System Unit -
Volume Flow" or "System Unit - Mass Flow").
Add. Line Mux -
Format
AUTO - OOS
!
Note!
The option is not active unless a number was selected in the parameter
"Add. Line Mux - Assign" (
Use this parameter to define the maximum number of places after the
decimal point displayed for the reading in the additional line.
Options:
XXXXX. - XXXX.X - XXX.XX - XX.XXX -X.XXXX
Factory setting:
X.XXXX
!
Note!
• Note that this setting only affects the reading as it appears on the
display, it has no influence on the accuracy of the system's calculations.
• The places after the decimal point as computed by the measuring device
cannot always be displayed, depending on this setting and the
engineering unit. In these instances an arrow appears on the display
between the measured value and the engineering unit (e.g.
1.2
→
kg/h), indicating that the measuring system is computing with
more decimal places than can be shown on the display.
"Display" Transducer Block/base index 1800:
Parameter
Write access with
operating mode
(MODE_BLK)
Description