Device Functions Proline Promag 55 FOUNDATION Fieldbus
8 Block SUPERVISION
Hauser
55
8.1.2
Function group OPERATION
SUPERVISION
J
⇒
SYSTEM
JAA
⇒
CONFIGURATION
800
⇓
OPERATION
804
Function description
SUPERVISION
→
SYSTEM
→
OPERATION
ACTUAL
SYSTEM CONDITION
(8040)
Use this function to check the present system condition.
User interface:
SYSTEM OK or the fault/notice message with the highest priority.
PREVIOUS SYSTEM
CONDITIONS
(8041)
Use this function to view the fifteen most recent fault and notice messages since
measuring last started.
User interface:
The 15 most recent error or notice messages
SIMULATION
FAILSAFE MODE
(8042)
Use this function to set the Analog Input and Totalizer function blocks to their defined
flow response modes in order to check whether they respond correctly. During this time,
message no. 692 "SIM. MEASURAND" appears on the display.
Options:
OFF
ON
Factory setting:
OFF
!
Note!
With the fieldbus, an active simulation is relayed to downstream function blocks and
higher-order control systems by means of the status "UNCERTAIN" of the output value
OUT (AI Block).
SIMULATION
MEASURAND
(8043)
Use this function to set all inputs, outputs and totalizers to their defined flow response
modes in order to check whether they respond correctly. During this time, the words
"SIMULATION MEASURAND" appear on the display.
Options:
OFF
MASS FLOW
VOLUME FLOW
Factory setting:
OFF
"
Caution!
• The measuring device cannot be used for measuring while this simulation is in
progress.
• The setting is not saved if the power supply fails.